SECTION 201-CONCRETE, MORTAR, AND RELATED MATERIALS

201-1 PORTLAND CEMENT CONCRETE.

201-1.1 Requirements.

201-1.1.1 General. Concrete shall consist of portland cement, concrete aggregates, water, and admixture when approved for use, in accordance with these provisions. Concrete will be specified by class or by compressive strength, When specified by class the concrete will be designated by a number, a letter, and a number. The first number is the weight of cement in pounds per cubic yard, the letter is the combined aggregate gradation, and the last number is the minimum compressive strength at 28 days. The concrete class used shall be in accordance with 201-1.1.2, unless otherwise specified. Concrete specified by compressive strength shall be designed by the Contractor in accordance with 201-1.1.3.

Concurrent with strength design criteria, concrete shall also be proportioned to provide the requisite durability to satisfy the exposure conditions imposed by either environment and/or service. Durability, in this context, refers to the ability of the concrete to resist deterioration from the environment or service in which it is placed. Concrete pro-portioned in accordance with ACI 318, Chapter 4, Durability Requirements, will meet this criteria.

Approved admixtures shall be in accordance with 201-1.2.4 and 201-1.2.5. Additional cement is permitted to obtain high early strength in concrete, except that total cement shall not exceed 700 pounds per cubic yard unless otherwise approved by the Engineer. Type III cement (High Early Strength) may be used in lieu of Type II cement in the same batch quantities as specified or approved for Type n cement. Where Type V cement is specified, provided the other provisions of 201-1.2.5 are satisfied, a combination of Type H cement and fly ash may be substituted.

Rapid-hardening hydraulic cement may be used when approved by the Engineer. The concrete mix shall conform to requirements of ASTM C 928. Admixtures may be used when approved by the Engineer.

201-1.1.2 Concrete Specified by Class. The concrete class and maximum slump for the various types of construction shall be as designated in the following table. The exact proportion of aggregates and water to be used in the concrete will determined by the Engineer from tests of the material to be used.

201-1.1.3 Concrete Specified by Compressive Strength. The Contractor shall determine the mix proportions of concrete specified on the Plans by its 28-day compressive strength within the minimum cement, maximum size coarse aggregate, and admixture limitations designed herein or in the Specifications. The concrete shall contain not less than 560 pounds of cement or cement and fly ash per cubic yard, in accordance with 201-1.2.5, for concrete strengths of 3,250 psi or greater.

Calcium chloride may be used only with the approval of the Engineer. Admixtures proposed for use shall be evaluated in accordance with 201-1.2.4.

 

 

TABLE 201-1.1.2 (A)

Type of construction

Concrete Class

Maximum Slump (inches)

Street Surface Improvements

Concrete pavement (not integral with curb)

520-A-2500

3

Curb, Integral Curb and Pavement, Gutter,

520-C-2500

4

Walk, Alley Aprons

520-C-2500P

4

Extruded Curb, Curb and Gutter

520-C-2500

2

520-D-2500

2

Sewer & Storm Drainage Facilities

Pipe Collars, Beam Support for Pipe, pre-cast Manhole components, Catch Basins,

560-C-32502

5

Sidewalk Culverts

565-C-3250P

4

Sidehill Drainage Facilities

500-C-2500

3

520-C-2500P

4

560-E-2500P

4

Pipe Bedding and Encasement, Anchors

450-C-20002

4

and Thrust Blocks, Wall support for Pipe

565-E-2000P

6

Tunnel Backfill

480-C-2000

5

490-C-2000P

5

Trench Backfill Slurry

100-E-100

5

Reinforced Structures

Bridges, Buildings, Retaining walls,

560-C-32502

4

And Tunnels

565-C-3250P

4

650-C-40003

4

660-C-4000P3

4

Cast-In-Place Piles

560-C-32502

4

565-C-3250p

4

Channels and Boxes, Invert

560-C-3250

4

565-C-3250p

4

650-C-40003

4

660-C-4000P3

4

Walls and Deck

560-C-3250

5

565-C-3250P

5

650-C-40003

4

660-C-4000P3

4

Miscellaneous

Street Light and Traffic signal foundations, Survey Monuments

560-C-3250

4

Fence and Guardrail Post Foundations

500-C-2500

5

Concrete Not Otherwise Specified

560-C-3250

5

565-C-3250P

4

Air Place Concrete, Method B

650-D-3250P

4

650-E-3250P

4

Course Masonry Grout

610-E-2000G

10

 

[Notes continued from Table 201-1.1.2 (A)]

1. Use limited to bedding concrete over which backfill will be placed not less than 40 hours after placement. For backfill after 24 hours, add 3 pints of calcium chloride. For backfill after 16 hours and removal of sheeting after 18 hours, use 660-C-3750 with 3 pints calcium chloride solution.

2. Use B Aggregate gradation when placing conditions permit.

3. 4000 psi concrete mixes require the use of a water reducing admixture conforming to the requirements of 201-1.2.4, "Admixtures."

4. Concrete mixes followed by a "P" have been designed to accommodate placement by a concrete pump. A pump mix may be substituted for a similar class mix and placed utilizing standard placement methods by the Contractor at its option. Said substitution, if made, shall be at the Contractor's expense.

5. Concrete mixes followed by a "G" have been designed to accommodate the grout requirements of Section 202, Masonry Materials.

The proposed mix design shall be evaluated from field tests of a trial batch conforming to the size of load, materials, proportions, slump, mixing and placing equipment, and procedures to be used in the actual work. The trial batch procedure may be waived when test data of prior performance of the proposed mix design is presented by the Con-tractor and approved by the Engineer. The Contractor may utilize any strength data on file with the Agency for this purpose.

When approved by the Engineer, trial batches may be placed in the Work at designated locations where concrete of a lower quality is specified. Concrete so placed will be considered for purpose of payment to be the type of concrete specified at that location.

Ten test cylinders shall be molded from the trial batch containing the maximum water content indicated by the mix design. Five of the cylinders shall be tested at 7 days in order to establish 7-day average compressive strength information. The remaining five cylinders shall be tested at no more than 28 days after molding and the average compressive strength of the five cylinders shall be at least 600 psi greater than the specified strength. The minimum strength of any one cylinder shall not be less than the specified strength. The placing of concrete specified by compressive strength shall not begin until the mix design has qualified in accordance with aforesaid test criteria. Should the source of materials or established procedures change, new trial batches may be required.

201-1.1.4 Test for Portland Cement Concrete. Portland cement concrete shall be sampled and tested in accordance with the following ASTM and California Tests:

1) Sampling Fresh Concrete C 172

2) Obtaining Drilled Cores C 42

3) Molding and Curing Specimens C 31

4) Compressive Strength C 39

5) Flexural Strength C 78

6) Slump C 143

7) Air Content C 173 or C231

8) Unit Weight Yield C138

9) Setting of Mortar C 191 or C 266

10) Mortar Cube Test Calif. Test 515

11) Drying Shrinkage Calif. Test 530 (with admixture)

A compressive strength test shall consist of the average strength of two cylinders fabricated from a single load of concrete, except that if any cylinder shows evidence of improper handling, molding, or testing, it shall be discarded and the strength test shall consist of the strength of the remaining cylinder.

The frequency of sampling will be determined by the Engineer. The Contractor shall afford the Engineer all reasonable access, without charge, for the procurement of samples of fresh concrete at time of placement.

Concrete compressive strength tests representing concrete which has been placed shall attain the following 28-day strength: The average of any three consecutive strength tests shall be equal to or greater than the specified 28-day strength. Not more than 10 percent of the tests shall be less than the specified 28-day strength. No test shall be less than 85 percent of the specified 28-day strength.

Concrete represented by compressive strength tests which fails to meet the requirements of this subsection shall be removed from the Work. However, with approval of the Engineer, the concrete represented by the failing compressive strength tests may be cored for strength testing. Coring shall commence within 5 days of notification by the Engineer. Drilled cores shall be obtained by the Contractor in the presence of the Engineer and tested at the Contractor's expense in accordance with ASTM C 42 by a laboratory acceptable to the Engineer. Drilled cores having a minimum nominal diameter of 4 inches shall be obtained unless otherwise directed by the Engineer. A minimum of three cores shall be taken in each area represented by the failing 28-day compressive strength tests. Unless otherwise directed by the Engineer, the cores shall be tested wet following a 40-hour submergence. If each core produces compressive strength test results 85 percent or greater than the specified 28-day compressive strength, the concrete represented may be accepted with no further action required.

201-1.2 Materials.

201-1.2.1 Portland Cement. All cement to be used or furnished shall be Type II low alkali portland cement conforming to ASTM C 150, or Type IP (MS) portland-pozzolan cement conforming to ASTM C 595, unless otherwise specified. Either cement shall conform to the low alkali requirements of Table IA of ASTM C 150. Type IP (MS) cement shall contain no more than 20 percent pozzolan, which shall be inter-ground with clinker.

The Contractor shall furnish a Certificate of Compliance signed by the manufacturer identifying the cement and confirming compliance. Supporting test data will be furnished upon request by the Engineer.

Whenever suitable facilities are available for handling and weighing bulk cement, they shall be used. Otherwise, cement shall be delivered in original unopened sacks that have been filled by the manufacturer and are marked with his name or brand, type, and weight.

Cement shall be stored in such a manner as to permit ready access for inspection and sampling and suitably protected against contamination and moisture. Should any cement show evidence of contamination or be otherwise unsuitable, the Engineer may reject it and require that it be removed from the site.

All portland cement used in concrete for any individual structure shall be of the same brand and type unless otherwise approved by the Engineer.

201-1.2.2. Aggregates. Aggregates shall conform to the requirements prescribed in 200-1 and shall be approved by the Engineer prior to use. Aggregate shall be of such character that it will be possible to produce workable concrete within the limits of slump and water content in 201-1.1.2 and 201-1.3.3.

Methods of handling materials resulting in segregation, degradation, or the combining of materials which results in failure to meet specifications shall not be permitted. The free moisture content of sand shall not exceed 8 percent at the time of batching.

Aggregates shall be nonreactive when tested in accordance with ASTM C 289 and evaluated in accordance with Appendix A-1 of ASTM C 33. Aggregates found to be potentially reactive may be used only upon written approval of the Engineer.

201-1.2.3 Water. Water used for concrete shall not contain deleterious substances. Water shall not contain an amount of impurities that will cause a change in the time of setting of portland cement of more than 25 percent nor a reduction in relative mortar strength at 7 and 28 days of more than 10 percent compared to results obtained with distilled water.

In conventionally reinforced concrete work, water shall not contain more than 1,000 ppm of chlorides calculated as Cl, nor more than 1,000 ppm of sulfates calculated as SO4.

In prestressed concrete work, water shall not contain more than 650 ppm of chlorides calculated as Cl, nor more than 800 ppm of sulfates calculated as S04.

In nonreinforced concrete work, water shall not contain more than 2,000 ppm of chlorides calculated as Cl, nor more than 1,500 ppm of sulfates calculated as SO4.

201-1.2.4 Admixtures.

(a) General Requirements. Admixtures shall be used as specified or approved by the Engineer, and measured into each batch in liquified form by a mechanical dispensing device and method approved by the Engineer. The quantity dispensed shall not vary more than 5 percent from the quantity specified. If more than one admixture is used, each shall be dispensed by separate equipment in liquid form. Calcium chloride and chloride ions in excess of 1 percent by weight shall not be used in prestressed concrete. Calcium chloride may be used in reinforced concrete, upon approval of the Engineer. Admixtures to be used in grouting ducts in prestressed units shall not contain chloride ions in excess of 0.25 percent by weight of admixture.

Samples of the admixture proposed for use shall be submitted by the Contractor to the Engineer sufficiently in advance of their intended use to determine compliance with specified requirements. Approval to use an admixture shall not relieve the Contractor of the designated concrete strength requirements.

(b) Air-entraining Admixtures. Air-entraining admixtures shall conform to ASTM C 260. Tests by an approved laboratory shall provide sufficient data to determine the time-strength characteristics of the concrete mix with the admixture.

When the air-entraining agent consists of a vinsol resin-water solution that has been neutralized with caustic soda (sodium hydroxide), the Con- tractor may use such air-entraining admixtures without presenting test data. In lieu of test data, the Contractor shall furnish a certificate, signed by the manufacturer, attesting to this fact and staling the ratio of sodium hydroxide to vinsol resin, the percentage of solids based on residue dried at 105°C and that no other additive or chemical agent is present in this solution.

The concentration of dilution of the admixture shall be such that it is dispensed into each batch of concrete at a rate of not less than 1/2 fluid ounce per 100 pounds of cement.

Adjustments shall be made in the weights of aggregates used per batch to compensate for changes in yield due to air-entrainment.

If the Contractor elects to use an air-entraining admixture, the Engineer may require that additional cement be added to the concrete mixture when air content exceeds 4 percent. In no case shall air content exceed 6 percent.

The air content shall not deviate from the percentage specified or permitted by more than 2 1/2 percentage points.

(c) Water Reducing, Set Retarding, and Accelerating Admixtures. These admixtures, other than calcium chloride, shall conform to ASTM C 494, and shall not be used in greater dosages than those recommended by the manufacturer or permitted by the Engineer. The permitted dosage of the admixture shall not exceed that which will result in an increase in the drying shrinkage of the concrete in excess of 20 percent when used in precast or prestressed concrete, or 10 percent when used in any other structural concrete. The strength of concrete containing the admixture in the amount proposed shall, at the age of 48 hours and longer, be not less than that of similar concrete without the admixture. The admixture shall not adversely affect the specified air content, unless permitted by the Engineer.

(d) Calcium Chloride. When calcium chloride is permitted or required to accelerate setting time and to reduce the time necessary for the concrete to reach its specified strength, it may be processed from either a brine solution or flake. If prepared from flake it shall conform to ASTM D 98. The calcium chloride solution shall contain not less than 32 percent of anhydrous calcium chloride and the hydrogen ion concentration (pH) shall be not more than 10.4 nor less than 6.0. Calcium chloride solution shall be used at the rate of not more than 3 pints per 100 pounds of cement.

201-1.2.5 Fly Ash.

(a) General. Fly ash may be used in a concrete mix when approved by the Engineer. The amount of fly ash and portland cement used shall be based upon trial batches in accordance with 201-1.1.3. Fly ash shall not be used with Type IP (MS) or Type III portland cement.

Class C fly ash shall not be used where sulfate resistant concrete is required. Where Type V portland cement is specified for sulfate resistance, Type II portland cement and Class F fly ash may be used. Class F fly ash may be used as an addition to Type V portland cement.

The Contractor shall furnish a Certificate of Compliance signed by the supplier identifying the type of fly ash and staling that the fly ash complies with ASTM C 618 and these specifications. Supporting test data shall be furnished when requested by the Engineer. All testing and sampling procedures shall conform with ASTM C 311.

Separate silo storage facilities shall be provided. Suitable facilities shall be provided to discharge the fly ash into the cement hopper in accordance with 201-1.3.1. Fly ash shall be stored in such a manner as to permit ready access for the purpose of inspection and sampling and be suitably protected against contamination or moisture. Should any fly ash show evidence of contamination or be otherwise unsuitable, the Engineer may reject it and require that it be removed from the site.

All fly ash used in concrete for any individual structure shall be from the same source and of the same class in combination with the same source and type of portland cement, unless otherwise approved by the Engineer.

(b) Class F Fly Ash. Class F fly ash shall conform to ASTM C 618 and the following specifications:

Loss on ignition 4% maximum

803 content 3% maximum

Moisture content 1% maximum

R-Factor* (only required 0.75% maximum

where Sulfate Resistance

Concrete is specified)

*R=(% CaO5)

(% Fe2O3)from fly ash oxide analysis.

Class F fly ash, as a percent by weight of total cementitious material, shall not exceed 20 percent, unless otherwise approved by the Engineer.

(c) Class C Fly Ash. Class C fly ash shall conform to ASTM C 618 and the following specifications:

Loss on ignition 2% maximum

803 content 4% maximum

Moisture content 1% percent

Class C fly ash, as a percent by weight of total cementitious material, shall not exceed 30 percent, unless otherwise approved by the Engineer.

201-1.3 Proportioning.

201-1.3.1 General. Aggregates and cement shall be proportioned by weight except that when the amount of concrete required for any one contract is 10 cubic yards or less, the materials may be measured by volume. Materials that are proportioned by volume shall be measured in containers of known capacity.

Weigh hoppers shall be charged from bins located directly over them or from conveyor belts. When conveyor belts are used, there shall be a separate belt for each size aggregate. There shall be a moisture meter installed, accurate within I percent of actual moisture content, to indicate moisture in the sand.

Bulk cement shall be weighed in an individual hopper and kept separate from the aggregates until ingredients are released for discharge. The cement hopper shall be attached to a separate scale for individual weighing.

The amount of water added to the mixture shall be measured into the mixing drum through a valve with a positive cutoff. When water is measured by weight, it shall be weighed on a separate scale.

Whenever a portable batch plant is set up at a new location the scale assemblies shall be inspected and certified regardless of the date the scales were last tested.

Scales utilized in proportioning shall be either spring-less dial, multiple beam, or solid-state digital strain gage transducer. Scale graduation shall be no greater than the following:

Aggregate Scales 25 Lbs.

Cement Scales 5 Lbs.

Water Scales 5 Lbs.

If a multiple beam type scale is used, the scale shall be provided with an indicator operated by the main beam which will give positive visible evidence of over or under weight. The indicator shall be so designed that it will operate during the addition of the last 400 pounds of any weighing. The overtravel of the indicator hand shall be at least one-third of the loading travel. Indicators shall be enclosed against moisture and dust.

Weighing equipment shall be insulated against vibration and movement of other operating equipment in the plant. When the entire plant is running, the scale reading at cutoff shall not vary from the weight designated by more than 1 percent for cement, 1 percent for water, 1-1/2 per-cent for any size of aggregate, nor 1 percent for the total aggregate in any batch.

201-1.3.2 Combined Aggregate Gradings. If the combined aggregate grading conforms to the grading of its designated class, the individual grading required by 200-1.4 and 200-1.5 may be waived. The combined aggregates shall conform to the gradings specified in the following table:

TABLE 201-1.3.2 (A)

Percentage Passing Sieves

Sieve Size

Grading A

Grading B

Grading C

Grading D

Grading E

2"

100

100

1 1/2"

95-100

95-100

100

1"

64-80

80-96

95-100

3/4"

55-71

64-80

77-93

100

100

3/8"

37-53

40-52

50-70

92-100

90-100

No. 4

32-42

35-45

39-51

42-60

60-80

No. 8

25-35

28-38

31-41

33-47

50-70

No. 16

18-28

21-31

22-32

22-38

33-53

No. 30

10-18

10-20

12-22

17-25

19-35

No. 50

3-9

3-9

3-9

6-12

5-15

No.100

0-3

0-3

0-3

1-5

2-6

No.200

0-2

0-2

0-2

0-2

0-2

201-1.3.3 Concrete Consistency. The amount of water added at the mixer shall be regulated to take into account the free water in aggregates. Free water is defined as the total water minus the water absorbed by the aggregate in a saturated surface-dry condition.

The amount of water used in the mixture shall not exceed the amount necessary to permit practical placement and consolidation of the concrete. Total free water in the mixture shall not exceed an amount producing the maximum slump specified in 201-1.1.2, and shall not exceed amounts shown in the following:

TABLE 201-1.3.3 (A)

Pounds Per Cubic Yard of Concrete

Slump

In Inches

Aggregate1 Grading

1

2

3

4

5

A

270

280

290

300

310

B

275

285

295

305

315

C

290

300

310

320

330

D

320

335

350

365

375

E

335

350

365

380

395

1. When the coarse aggregate is composed solely of crushed rock, the above values may be increased up to 20 pounds of water per cubic yard.

When adverse or difficult conditions affect the placement of concrete, the Engineer may authorize a greater slump to be used, provided the cement is increased. Water shall be added at a ratio not to exceed 32 percent of added cement per cubic yard of concrete, and such additional water and cement shall be provided at the Contractor's expense.

201-1.4 Mixing.

201-1.4.1 General. Machine mixing will be required in all cases other than those in which it would obviously prove to be impractical, in which case hand mixing is permitted. Mixing shall be commenced as soon as possible after the cement is placed in contact with the aggregates, but in no event shall the intervening period exceed 30 minutes.

All concrete mixers shall be of such design and construction and so operated to provide a properly mixed concrete with uniform distribution of ingredients. Mixers shall be maintained properly and be in working order and not have any aluminum parts which will have direct contact with concrete.

201-1.4.2 Paving and Stationary Mixers. Paving and stationary mixers shall be equipped with an accurate automatic timing device so designed and constructed as to lock the discharge lever. The regulation setting of this device shall be under the supervision of the Engineer. Water control equipment shall also be provided with each concrete mixer.

The proper proportions of aggregate, cement, and water for each batch of concrete shall be placed in the mixer and mixed for a period of not less than I minute (1-1/2 minutes for reinforced concrete).

The rotating speed at which the mixer shall be operated shall conform to that recommended by manufacturer. The total volume of materials in any one batch shall exceed neither the water level capacity of the mixer nor the manufacturer's guaranteed capacity of the mixer.

201-1.4.3 Transit Mixers. The type, capacity, and manner of operation of the mixing and transporting equipment for ready-mix concrete shall conform to the current "Standards for Operation of Truck Mixers and Agitators of the National Ready-Mixed Concrete Association" and the 'Truck Mixer and Agitator Standards of the Truck Mixer Manufacturers Bureau". Transit mix concrete trucks shall be equipped with an automatic device for recording the number of revolutions of the drum during the mixing period. Each mixer and agitator shall have attached thereto in a prominent place, a metal plate or plates, installed by manufacturer on which is plainly marked the capacity of the drum in terms of the volume of mixed concrete and the speed of rotation for the agitating and mixing speeds of the mixing drum or blades.

Each mixer shall have an identification number painted on it that can be easily read from the batching platform.

The total volume of materials introduced into the mixer shall not exceed the manufacturer's guaranteed mixing capacity. If the concrete so mixed does not meet the uniformity requirements, the amount of materials charged into the mixer shall be reduced.

The drum of the mixer shall be completely emptied of any previously mixed load. The proper proportions of aggregate, cement, and water for each load of concrete shall be placed in the mixer and shall be mixed between 70 and 100 revolutions at the designated mixing speed. Additional revolutions of the drum shall be at designated agitating speed. The revolving of the drum shall be continuous until the concrete is completely emptied from the drum.

When concrete is being placed for pavement or concrete structures, all wash water shall be emptied from the mixer before any portion of the succeeding load is placed. For all other work, the mixer shall be empty or may carry 10 gallons of water in the drum. Adequate control of ready-mixed concrete requires additional added water mixed into the batch at discharge point. This water shall be mixed for a minimum of 30 revolutions at rated mixing speed. Water shall not be added to the load during transit.

The total elapsed time between addition of water at the batch plant and discharging the complete mix shall not exceed 90 minutes. Under conditions contributing to quick setting, the Engineer may reduce this time.

The Engineer shall be provided with a legible certified weighmaster certificate. When mix proportions have been designated for a project and are identified by number the Engineer may accept a legible certified weighmaster certificate which shall contain the following information:

1) Name of Vendor

2) Name of Contractor

3) Project Location

4) Number of cubic yards in the load

5) Mix designation number

6) Amount of water added at the plant (including water in aggregates)

7) Maximum Allowable water

8) Time and date of batching

When the mix proportions are not designated by number, or when required by the Engineer, the certificate shall contain the following additional information:

1) Actual weights of cement and of each size of aggregate

2) Brand and type of cement

3) Brand, type and amount of admixture.

Space shall be provided on the certificate so that the amount of water added on the job may be indicated.

201-1.4.4 Hand Mixing. Hand mixing is permitted when the amount of concrete required is less than 1 cubic yard. Hand-mixed concrete shall be mixed on a watertight platform or in a mortar box in batches not to exceed 1/3 cubic yard each. The aggregates shall be spread in a uniform layer over which the required quantity of cement shall be evenly distributed. The entire batch shall be turned with shovels until the ingredients are throughly blended before adding water. After adding the proper amount of water, the batch shall again be turned with shovels until a uniform consistency is obtained. Methods of hand mixing which allow the loss of mixing water will not be permitted.

201-1.5 Transporting Batched Materials and Mixed Concrete. The compartments of trucks or other equipment used for the purpose of transporting proportioned dry aggregate and cement, or mixed concrete, shall be suitably constructed to protect and prevent loss or leakage of con-tents during charging, transit, or discharging.

201-2 STEEL REINFORCEMENT FOR CONCRETE.

201-2.1 General. Bar, wire, and wire mesh reinforcement shall conform to dimensions and details indicated on the Plans or otherwise prescribed. Before placed in any concrete work, it must be thoroughly cleaned.

201-2.2 Reinforcing Steel. Unless otherwise specified, reinforcing steel shall be either Grade 40 or Grade 60 billet steel conforming to ASTM A 615. Steel bending processes shall conform to the requirements of Manual of Standard Practice of the Concrete Reinforcing Steel Institute. Bending or straightening shall be accomplished so that the steel will not be damaged. Kinked bars shall not be used.

201-2.3 Wire Reinforcement. Wire reinforcement shall in all respects fulfill requirements prescribed in ASTM A 82.

201-2.4 Wire Mesh Reinforcement. Mesh reinforcement shall conform to ASTM A 185. The gage of the wire and the dimensions of the mesh shall be as shown on the Plans or in the Specifications. The wire mesh reinforcements shall be so constructed as to retain its original shape and form during necessary handling. The effective cross-sectional area of the wire shall be equal to that specified or indicated on the Plans.

201-2.5 Samples for Testing.

201-2.5.1 General. No reinforcing steel will be accepted until it has been approved by the Engineer. Samples shall be taken from bars selected by the Engineer and cut in the Engineer's presence. The Contractor shall furnish a certified mill test report for each heat or size of steel when required by the Engineer.

201-2.5.2 Reinforcing Steel Bars. Two sample bars, cut from different bars and 3 feet in length for sizes # 3 through # 5 and 5 feet in length for size # 6 and larger, shall be taken from each bar size and heat number delivered to the job site on a cumulative tonnage basis in accordance with the following schedule:

TABLE 201-2.5.2 (A)

Bar sizes (Number)

Cumulative Weight of Steel per Bar Size Delivered to Job Site (Tons)

2

1/2

3

1

4

2

5

3

6

4

7

5

8

7

9

9

10

11

11

13

14

20

18

35

Note: At least two sample bars shall be taken from each bar size.

201-2.5.3 Wire Reinforcement. One sample consisting of two pieces, each 3 feet long, shall be taken from each 2-ton lot or less of each size of wire delivered to the job site,

201-2.5.4 Wire Mesh Reinforcement. Two samples of a size suitable for testing shall be taken from each 3,000 square feet of fabric or fraction thereof.

201-3 EXPANSION JOINT FILLER AND JOINT SEALANTS.

201-3.1 General. This section specifies joint fillers and sealants to be used for treating joints in portland cement concrete.

All joints which are to be sealed shall be formed with filler. The filler shall be placed in correct position before concrete is placed against it. Holes or joints in the filler shall be filled with mastic to prevent the passage of mortar or concrete from one side of the joint to the other.

201-3.2 Premolded Joint Filler. Premolded joint filler material shall consist of premolded strips of a durable resilient material.

Unless otherwise specified, premolded joint filler shall be one of the following:

Preformed Expansion Joint Filler (Bituminous) ASTM D994

Nonextruding and Resilient Filler (Bituminous) ASTM D 1751

Nonextruding and Resilient Filler (Non-bituminous) ASTM D 1752

201-3.3 Polystyrene Joint Filler. Commercial quality expanded polystyrene foam blocks and planks shall be furnished by the Contractor and installed in place as shown on the Plans. The foam shall be composed of non-interconnecting cells. Expanded polystyrene shall have a flexural strength of 35 psi and a compressive yield strength of between 16 and 40 psi at 5 percent compression.

Surfaces of expanded polystyrene against which concrete is to be placed shall be faced with hardboard. Hardboard shall be 1/8-inch-minimum thickness conforming to Federal Specifications LLL-B-810, any type. Other facing materials may be used, provided they furnish equivalent protection. All boards shall be held in place by nails, water-proof adhesive, or other means approved by the Engineer.

201-3.4 Type "A" Sealant (Two-Part Polyurethane Sealant). The sealant shall be a polyurethane sealant furnished and placed in accordance with the Specifications for "Two-Component Machine-Mixed Polyurethane Sealant" (State Specification 8030-61 J-01).

Polyethylene foam shall be commercial quality, with a continuos impervious, glazed top surface, suitable for retaining the liquid polyurethane sealant in the joint while hardening.

A primer, furnished by the manufacturer of the sealant, shall be applied to the sides of the groove and to all exposed vertical surfaces in the joint prior to placing the polyurethane sealant. The primer shall be dry prior to placing sealant. Contamination of the completed primer with foreign material will be cause for rejection of the primed surface.

201-3.5 Type "B" Sealant (Preformed Elastomeric Sealant). The sealant shall be a preformed elastomeric joint seal conforming to specifications of ASTM D 268 and the following requirements:

The manufacturer shall designate the minimum uncompressed width of each size of seal to be furnished. Any seal which has a minimum uncompressed width, measured at any point in the height of the seal, less than that designated by the manufacturer shall not be used.

Seals delivered to the job that have dimensional or shape tolerances of such magnitude that the seal will not function as specified shall not be used.

The seal shall consist of a multi-channel, nonporous, homogeneous material furnished in a finished extruded form, and shall be furnished full length for each joint with no more than one shop splice in any 60-foot length of seal. Field splices shall not be used.

The adhesive used to splice the seal shall be an effective bonding agent and shall be resistant to water and ozone. The lubricant adhesive shall conform to State Specification 701-80-30. All abutting surfaces of shop splices shall be bonded together with adhesive. Shop splices shall have no visible evidence of bond failure.

After the seal has been installed in the joint, shop splices shall have no visible offset of the exterior surfaces and there shall be no evidence of bond failure at the abutting surfaces of the splices.

At all open ends of the seal, each cell of the elastomeric joint seal shall be filled to a depth of 4 inches with commercial quality open cell polyurethane foam, or closed by other methods subject to Engineer approval.

Tests of elastomeric joint seals will be conducted in accordance with Calif. Test 673.

201-3.6 Type "C" Sealant (Asphalt-Latex Emulsion Joint Sealant). Asphalt-latex emulsion joint sealant shall be designated for mixing and application by hand methods and shall be suitable for use at temperatures above 50°F. The sealing compound shall be an emulsion consisting of paving asphalt. Grade AR-1000, conforming to requirements of 203-1 emulsified with rubber latex in a suitable emulsifying agent. Rubber latex shall be natural rubber or synthetic latex containing approximately 40 percent solids. The resulting emulsion shall consist of a minimum of 55 percent paving asphalt and a minimum of 36 percent rubber latex.

A setting agent shall be provided in the form of a paste to be added at the rate of approximately 3 fluid ounces per gallon of emulsion.

The joint sealant shall comply with the requirements of Table 201-3.6 (A).

201-3.7 Type "D" Joint Sealant (Hot-Poured Rubber-Asphalt Joint Sealant). Hot-poured rubber asphalt joint sealants shall conform to requirements of ASTM D 1190. They shall be applied in accordance with manufacturer's recommendation and 303-1.8.7.

TABLE 201-3.6 (A)

Determination

Test Method No.

Requirements

Remarks

Furol

Viscosity at 77O F

ASTM D 88

80-250 Sec.

Before adding setting agent.

Sieve Test

ASTM D 244

1% Max.

Before adding setting agent.

Penetration1 at 77o F

Calif. 418

50-150

Immediately after mixing, the material is poured into a 6 ounce deep ointment can and the specimen allowed to stand in air at a temperature of 770 ± 20 F for a period of 24 hours. It is then penetrated with a grease cone under a total load of 150g in accordance with ASTM D 217

Elasticity1

Calif. 418

70% Min.

Immediately after mixing, the material is placed in an aluminum pan and cured for 24 hours at 1150 ± 20F. Specimen shall be tested in modified ductility mold per test method.

Total Solids2

Calif. 418

70% Min.

3 to 5g of freshly mixed material is place in an aluminum pan and dehydrated in a suitable oven maintained at a temperature of 2000 ± 30F for a period of three hours

Setting Time2

Calif. 418

60 min. Max.

Material is poured into a 6 ounce deep ointment can and penetration checked each 15 minutes. Time is recorded when penetration is less than 200.

1. Mixing ratio of material: Add 10 ±0.1g. of sodium fluosilicate powder to 200g. of emulsion component.

2. Mixing ratio of material: Add 12mL of setting agent component to 8 fluid ounces of emulsion component.

201-3.8 Type "E" Joint Sealant (Polysulfide Polymer and Rubber Rod). Polysulfide polymer type joint sealant shall be a two-component, plastic, rubber like, cold-applied joint sealant. This material shall resist the intrusion of foreign materials into the joint throughout repeated cycles of expansion and contraction.

The joint sealant shall be packaged in sealed containers identified by the name of the manufacturer, lot number, and date, and bear instructions for mixing and application. Accelerator containers shall be marked "A", and polysulfide containers shall be marked "B". The weight of component "A" in the mixture shall not less than 10 percent of component "B". Minimum polysulfide content of the mixture shall be 20 percent by weight.

Upon opening the container, component "B" shall not exhibit more than a slight degree of "skinning" on the surface of the material.

The joint sealant shall comply with the following requirements when laboratory mixed materials are tested in accordance with Calif. Test 413:

TABLE 201-3.8 (A)

Determination

Requirements

Viscosity, 5 minutes after mixing, poises

200 to 350

Application time [pot life of time to reach 2000 poises at 770F, hours minimum

1

Penetration at 770F after aging 24 hours at 770F

150 max

Nonvolatile content, percent

88 min.

The following tests are to be performed on the mixed material after 96 hours of aging at 77 F:

TABLE 201-3.8 (B)

Determination

Requirements

Penetration at 770F

50 to 120

Penetration at 1580F

175 max.

Resilience at 770F, percent

70 min. 60 min.1

Resilience at 1580F, percent

60 min. 50 min.1

Bond to concrete, 100% extension, dry at -200F

No failure

Bond to concrete, 50% extension, wet at -200F

No failure

The following test is to be performed on the sample from the resilience test above, oven-aged for 7 days at 158°F:

TABLE 201-3.8 (c)

Determination

Requirements

Resilience of oven-aged sample after 7 days at 770F, percent

70 min. 60 min.1

1. This requirement applied if the penetration at 77°F, after 96 hours aging at 77°F, is 100 to 120.

 

 

The rubber rod shall be a cellular synthetic rubber, either butyl or neoprene, of circular cross section with continuous skin impervious to water. It must comply with the following requirements:

TABLE 201-3.8 (D)

Determination

Requirements

Specific gravity (Bulk)

0.30 to 0.50

Surface hardness, durometer (Fig. 1) ASTM D 2240

60 to 85

Water absorption, by weight, one inch head at 750F, for 24 hours, percent

5 max.

Resistance to ozone, ASTM D 470 (except 30 minute exposure, at 70 ± 10 mg/L ozone, at 850F)

No cracks

201-3.9 Test Report and Certification. When requested by Engineer, the Contractor shall provide at delivery time, certified copies of the vendor's test report. This shall indicate the vendor name, type of joint sealant, date and point of delivery, quantity, ticket number, lot number, and results of the required test. The test report shall be signed by an authorized representative of the vendor. The certified test reports and testing required in connection therewith shall be without cost to the Agency.

201-4 CONCRETE CURING MATERIALS.

201-4.1 Membrane Curing Compounds.

201-4.1.1 General. Curing compound shall consist of a liquid which, when applied to fresh concrete, will form a continuous membrane over the exposed surfaces of the concrete. Curing compounds shall conform to the requirements of ASTM C 309 Class B (Resin Type Only), except the loss of water shall not exceed 0.15 kilogram per square meter in 24 hours nor 0.45 kilogram per square meter in 72 hours when tested in accordance with ASTM C 156.

Concrete curing compounds are designated by type as follows:

Type 1 - Clear or translucent without dye.

Type 1 -D - Clear or translucent with fugitive dye.

Type 2 - White pigmented

Unless otherwise stated in the Plans or Specifications, Type 1-D shall be used, except that Type 2 shall be used for the top surface of bridge decks. Curing compounds which contain such coloration as to be easily visible following application shall be considered as meeting the fugitive dye requirement.

All compounds shall be furnished by the Contractor and shall be delivered ready-mixed in sealed original containers labeled in accordance with ASTM C 309 and with the date of the manufacture. At the time of use, pigmented curing compounds shall be maintained in a thoroughly mixed condition. Containers of curing compound shall remain air-tight when not in use.

201-4.1.2 Application. Curing compound shall be applied in two coats according to manufacturer's directions and 303-1.10. The direction of application of the second coat shall be perpendicular to the first. The second coat shall be applied when the first coat is dry to the touch, but not later than 4 hours after the first coat was applied.

The rate of application shall be such that the com-pound forms a continuous, unbroken film when applied to the work and shall not be less than the rate used when tested for water retention.

Application of the curing compound to the concrete shall commence as soon as the finished surface of the concrete reaches a uniformly damp appearance with no free water on the surface. At any point, the application rate shall be within 50 square feet per gallon of the nominal rate and the average application rate shall be within 25 square feet per gallon of the nominal rate specified when tested in accordance with California Test 535.

201-4.2 Sheet Curing Materials.

201-4.2.1 General. Sheet curing materials are designated by type as follows:

Type 1 - Waterproof Paper

Type 2 - Polyethylene Film

Type 3 - White-Burlap-Polyethylene Sheet

Type 4 - Burlap

Types 1,2, and 3 sheet curing materials shall conform to the requirements of ASTM C 171, Standard Specification for Sheet Materials for Curing Concrete.

201-4.2.2 Burlap. Burlap shall weigh not less than 10 ounces per linear yard, 40 inches wide.

201-4.3 Test Report and Certification. The Contractor shall provide, when requested by the Engineer, certified copies of vendor's test report showing compliance with ASTM C 309 and these specifications. The testing and the report required shall be supplied without cost to the Agency.

201-5 CEMENT MORTAR

201-5.1 General. Cement mortar shall consist of port-land cement, sand, and water. Cement and sand shall first be combined in the proper proportions, and then thoroughly mixed with the required amount of water.

Cement mortar shall be designated by class and pro-portioned by loose volume as shown in Table 201-5.1 (A). The quantity of water to be used in the preparation of mortar shall be only that required to produce a mixture sufficiently workable for the purpose intended.

Mortar shall be used as soon as possible after mixing and shall show no visible signs of setting prior to use. Retempering of mortar will not be permitted.

 

TABLE 201-5.1 (A)

Mortar Designation

. Proportions

Class

Parts Cement

Parts Sand

A

1

1

B

1

1 1/2

C

1

2

D

1

2 1/2

E

1

3

F

1

3 1/2

201-5.2 Cement. Cement shall conform to 201-1.2.1.

201-5.3 Sand. Sand shall conform to requirements of 200-1.5.3. In proportioning the sand it shall be measured loose (without shaking or compacting) in measuring boxes or other suitable containers of known capacity.

201-5.4 Water. Water shall conform to 201-1.2.3.

201-5.5 Admixtures. No admixture shall be used in mortar unless approved by the Engineer.

201-5.6 Quick-Setting Grout. Quick-setting grout shall be a high strength nonstaining grout approved by the Engineer. It shall reach an initial set within 90 minutes at 70°F and reach minimum compressive strength of 25 00 psi within 24 hours. Shrinkage shall be less than 0.1 percent when tested, using the test procedures of ASTM C 596. The grout shall be mixed, handled and placed in accordance with manufacturer's instructions.